A momentary push button switch closes its contact while the button is held and opens it again the moment the button is released. That is the whole definition, and it is defined in the standard rather than left to habit: under IEC 60947-5-1, a momentary action contact returns to its rest state when the actuator is released, while a maintained action contact stays where it was put until it is operated a second time.
The distinction sounds academic until it reaches a control circuit. A momentary push button switch cannot hold a machine in the run state by itself; a maintained switch used for a jog function can leave a machine running after the operator has walked away. Most of what follows is about telling the two apart on a datasheet, and about the numbers that decide whether the button survives the circuit it is wired into.
What a Momentary Push Button Switch Means in the Standard
A momentary push button switch has a rest position, a travel, and a spring that returns it. Three details in that sentence matter when you are specifying one.
- Rest state. The contact block defines what happens at rest. A normally open (NO) block is open at rest and closes while pressed; a normally closed (NC) block is closed at rest and opens while pressed. The operator itself does neither — the block does, and the same button can carry either.
- Travel and force. On a typical 22 mm momentary push button switch the actuating travel is around 5.8 mm, with an operating force of roughly 2 N on an NC block and a little over 3 N on an NO block. That difference is why a stop button feels lighter than a start button on the same panel.
- Return speed. The rebound is fast — under about 1 ms on a good operator. The contact does not ease open; it snaps back, which is what keeps the break clean when the operator lets go.
None of that is visible from the front of the panel, which is why two buttons that look identical can behave completely differently in a circuit.
Momentary, Maintained and Latching: Three Words for Two Behaviours
Momentary and maintained are the two behaviours the standard defines. Latching is the word most people use for maintained, and in switch catalogues it is used loosely enough to be worth checking.

| Momentary | Maintained | |
|---|---|---|
| State while held | Operated | Operated |
| State on release | Returns to rest | Stays operated |
| How it is reset | Release the button | Operate it again |
| Typical use | Start, jog, reset, hold-to-run pendant, doorbell | Mode selection, power on/off, isolator |
| Failure if the wrong one is fitted | Machine stops when the operator lets go | Machine keeps running after the operator walks away |
Both are legitimate. The problem is that a maintained switch is safer-looking — it holds the state you asked for — while a momentary one is safer in the specific case that matters most: the operator’s hand leaving the control. Jog functions, inching, and any pendant control where the machine should stop when the operator lets go must be momentary, and that requirement comes from the machine’s risk assessment, not from the switch catalogue.
Selector switches are the usual place the two get confused, because a three-position selector is normally maintained while a spring-return version of the same body is momentary. If the panel drawing shows a spring-return symbol and the ordered part has detents, the panel will not behave as drawn.
NO and NC: The Operator Does Not Decide, the Block Does
A momentary push button switch is not inherently normally open. The head, the bezel and the body are mechanical; the electrical behaviour comes from the contact block snapped onto the back, and the same operator can carry an NO block, an NC block, or both.
That is also where the terminal numbers come from. On a standard industrial block the NC pair is marked 11 and 12 and the NO pair 13 and 14, so the second digit tells you the function and the first tells you which contact it belongs to. Reading those numbers correctly is the difference between wiring a stop circuit and wiring a start circuit into the same button. The full numbering system, including stacked blocks and illuminated versions, is set out in the push button switch pinout guide.
The practical consequence is that a spare button on the shelf is not a spare for a specific function. Swap an NO block for an NC block and the panel behaves in the opposite sense, with no visible change on the front.
What Is Inside a 22 mm Momentary Push Button Switch

From the front: a bezel, a cap, and a collar that clamps the body to the panel through a 22 mm hole. Behind the panel: a plunger, a return spring, and one or more contact blocks.
Most industrial blocks are double-break, meaning each contact has two gaps in series. That matters for two reasons. It roughly doubles the breaking capacity for the same contact gap, and it means an NC block can be built with positive opening — a mechanical guarantee that the contact opens when the button is pressed, rather than relying on the spring and the arc behaviour. Positive opening is what makes a stop circuit trustworthy; it is covered further down.
The other choice is slow-make versus snap-action. A slow-make block opens and closes at the speed of the plunger, which is fine for control circuits and is what allows positive opening to be guaranteed. A snap-action block uses an over-centre spring to close quickly regardless of how slowly the button is pressed, which suits low-current and dry-circuit applications where contact bounce matters more than breaking capacity.
The Utilisation Category Decides Whether the Button Survives
A 22 mm momentary push button switch looks like it can switch anything. It cannot, and the datasheet number that says so is the utilisation category.
| Category | Load | Typical rating of a 22 mm block |
|---|---|---|
| AC-12 | Resistive or slightly inductive AC | Often 10 A at 230 V |
| AC-15 | Electromagnetic loads, AC (contactor coils, relays, solenoids) | About 6 A at 230 V, 4 A at 400 V, 2.5 A at 500 V |
| DC-12 | Resistive DC | Higher than DC-13, rarely the limiting figure |
| DC-13 | Electromagnetic loads, DC | About 10 A at 24 V, 3 A at 60 V, 1 A at 110 V |
Two things follow from that table, and both cause real failures.
The AC and DC ratings are not interchangeable. A block rated 6 A at 230 V AC is not a 6 A block at 230 V DC. DC has no natural current zero, so the arc has to be stretched and cooled by the mechanism alone; the DC-13 rating falls steeply as voltage rises. If the control circuit is 110 V DC, the same block that handles 6 A of AC may only be good for around 1 A.
An inductive load is not a resistive load. Switching a contactor coil means interrupting stored inductive energy. A block rated AC-12 for a resistive load will pit and eventually weld its contacts when it is used to switch a coil at the same current. The failure mode is unpleasant: a welded NO contact turns a momentary button into a permanently closed one, and the machine restarts as soon as power returns.
That is the mechanism behind most “the start button is stuck” faults. It is not a mechanical jam; the contact has welded, and the button was under-rated for the coil it was switching.
Why a Momentary Push Button Switch Cannot Be an Emergency Stop
A red mushroom head on a momentary push button switch is not an emergency stop, and fitting one is a safety defect rather than a specification choice.
An emergency stop device has to latch. Under IEC 60947-5-5 the actuator must stay in the operated position until a deliberate reset action is performed, and it must have a positive opening operation so that the NC contact is mechanically forced apart. A spring-return momentary button fails both requirements: it returns as soon as it is released, and its contact opens by spring action rather than by a guaranteed mechanical separation.
The confusion arises because the two look alike from the front. A genuine emergency stop uses a latching mechanism — twist to release, pull to release, or key release — inside a mushroom head that may be visually identical to a momentary one. If the head turns back by itself when you let go, it is not an emergency stop.
There is a related case that is correctly momentary: hold-to-run controls, where the machine is only permitted to move while the operator keeps holding the button. That is a deliberate use of the momentary behaviour, and it is specified from the risk assessment in exactly the same way an emergency stop is.
Where a Momentary Push Button Switch Belongs on a Panel

The pattern across most machine panels is consistent: momentary for commands, maintained for states.
- Start — momentary NO, wired through a holding contact so the circuit stays energised after release.
- Stop — momentary NC, wired in series with the coil circuit. Pressing it breaks the circuit; releasing it does not restart the machine, because the holding contact has already dropped out.
- Reset / acknowledge — momentary, usually NO into a PLC input, where a single pulse clears a fault. A maintained reset would hold the fault cleared and mask a recurring condition.
- Jog / inch — momentary by definition. The machine moves only while the button is held.
- Hold-to-run pendant — momentary, and often duplicated so that both hands are occupied.
- Mode selection — maintained selector, three positions. Changing mode is a state, not a command.
The interesting case is start and stop sharing a panel. Stop must be the NC block and start the NO block, and reversing them produces a panel that appears to work until the first time someone presses stop and the machine keeps running. Colour helps but is not a substitute: red for stop and emergency, green for start is convention, not a guarantee.
Wiring a Momentary Push Button Switch So It Latches
A momentary push button switch wired directly to a contactor coil gives you a machine that runs only while your finger is on the button. That is occasionally what you want; usually it is not.
The standard solution is a holding contact: an auxiliary NO contact on the contactor, wired in parallel with the start button. Pressing start energises the coil, the contactor closes, and its own auxiliary contact now maintains the circuit when the button is released. The stop button, in series with the whole thing, breaks that circuit and the holding contact falls out with it.
Three details are worth checking at commissioning. The holding contact must be on the same contactor, not on a separate relay that could drop out independently. The stop button must be NC so that a broken wire stops the machine rather than preventing it from stopping. And if the start signal goes into a PLC rather than a contactor, the latching happens in logic, so the input needs debounce — a mechanical button bounces for a few milliseconds and a fast scan cycle will see several edges.
The wiring itself, including terminal numbering and the 2, 4 and 5 pin configurations, is covered step by step in the push button switch wiring guide.
Life Expectancy and What Wears Out First
Mechanical and electrical life are separate figures, and the smaller one governs. A momentary push button switch is typically rated around 3 million mechanical operations; the same operator with a maintained action is often quoted lower, because the mechanism has more to do. Those numbers assume no electrical load.
Electrical life is the figure that matters in service, and it is always lower. It depends on the load: a button switching a PLC input at a few milliamps will last essentially forever, while one switching a contactor coil at AC-15 may be quoted at a fraction of the mechanical figure.
What actually fails first, in order: the contact, from arcing or welding under an inductive load; the return spring, from fatigue, which shows up as a button that feels soft and does not fully reset; and the panel seal, from UV and cleaning chemicals, which turns an IP65 button into an IP40 one without any visible change.
The spring failure is the dangerous one, because a button that does not fully return holds its NC contact open. On a stop circuit that means the machine cannot be started, which is at least fail-safe. On a start circuit it means the NO contact may stay partially closed, and the symptom is a machine that starts by itself.
Specifying a Momentary Push Button Switch in Five Lines
| What you are deciding | Options | How to choose |
|---|---|---|
| Action | Momentary or maintained | Command or state. Anything that must stop when released is momentary. |
| Contact | NO, NC, or both; 1 to 4 blocks | NO for start and reset, NC for stop and interlocks. Both when the button has to report its own position. |
| Operator | Flat, high, mushroom, illuminated, key | Gloved hands and panel density decide the head; illumination when the button must show state. |
| Body and seal | Plastic, chrome-plated metal, stainless; IP40 to IP67 | Wash-down and outdoor panels need the sealed metal versions; a plastic body at IP40 is fine inside a cabinet. |
| Rating | AC-15 / DC-13 figures at your control voltage | Check the coil or load against the category, not against a headline current. |
If the button is illuminated, add a sixth line: the lamp voltage. The illumination circuit is separate from the contact circuit, and a 24 V DC contact block tells you nothing about the LED behind the lens. Ordering a 230 V lamp for a 24 V panel is a common and entirely avoidable mistake.
The operator heads, block codes and lamp voltages for the range we build are listed on the push button switch and signal lamp page, alongside the matching AD169 signal lamps. If you are still choosing between families, the guide to push button switch types covers the wider picture, and the general guide to momentary switches covers the non-panel versions.
FAQ
What is the difference between a momentary and a latching push button?
A momentary button returns to its rest state when released; a latching (maintained) button stays in the operated state until it is pressed again. In circuit terms, momentary gives a pulse and latching gives a state.
Is a momentary push button switch normally open or normally closed?
Either. The behaviour comes from the contact block fitted to the back of the operator, not from the button itself. A momentary operator can carry an NO block, an NC block, or both at once.
Why does my machine stop when I release the start button?
Because the start button is wired directly to the coil without a holding contact. A momentary start needs an auxiliary NO contact on the contactor wired in parallel with the button, so the circuit maintains itself after release.
Can a momentary push button switch be used as an emergency stop?
No. An emergency stop must latch in the operated position and have positive opening of its NC contact, as required by IEC 60947-5-5. A spring-return momentary operator does neither, even if it has a red mushroom head.
What is the difference between AC-15 and DC-13?
Both cover electromagnetic loads — contactor coils, relays, solenoids — but one is for AC and one for DC. The DC rating is much lower at the same voltage because direct current has no natural zero crossing to help extinguish the arc, so never carry an AC figure across to a DC circuit.
How many operations does a momentary push button switch last?
Around 3 million mechanical operations is a typical figure for a 22 mm momentary operator. Electrical life is lower and depends on the load, so for a button switching a contactor coil the contact rating matters more than the mechanical figure.
Do I need an illuminated momentary button?
Only if the button has to show the state of the circuit. The lamp is on a separate circuit from the contact, so it needs its own supply and its own voltage. On a panel where an indicator lamp already shows the state, an illuminated button adds a failure point without adding information.
What is a spring-return selector switch?
A selector switch whose handle returns to the centre position when released. It is momentary in behaviour but has a selector head, and it is used where an operator has to hold a mode for as long as it applies — typically a spring-return position on a three-position selector.
Get the Action Right Before the Part Number
Almost every momentary push button problem traces back to one of three decisions made too early: the action (momentary or maintained), the block (NO or NC), and the rating (AC-15 or DC-13 at the actual control voltage). Get those three right and the rest is bezel, colour and seal.
Send us the control voltage, the load being switched and what the button has to do when it is released, and we will come back with the operator, the block code and the lamp voltage rather than a catalogue page.